Fuses, Capacitor Systems, and Overcurrent Protection
Toll Free  :  800.245.0583
Fax  :  586.979.9484
 

HomeAboutProductsServicesResourcesNewsContact Us

News > Fuses, Capacitor Systems, and Overcurrent Protection

Fuses, Capacitor Systems, and Overcurrent Protection

Fuses, Capacitor Systems, and Overcurrent Protection

Posted By Lauren Loudon / January 31, 2014
Frequently Asked Question: MZI capacitor installation instructions recommend the use of circuit breakers or fuses to meet NEC overcurrent protection requirements. Why is this necessary when the capacitor system is already fused?

Answer: The fuses installed in capacitor systems protect the capacitors from excessive currents resulting from a short circuit or voltage anomaly. Fuses are sized as high as 250% to 300% of the rated current and are not intended as a substitute for the overcurrent device per NEC requirements.

Operating voltage determines the current drawn by the capacitor. At 480 volts, the capacitor current is 1.2 amps per kVAr. For a 50 kVAr unit or step, the current is 60 amps. Capacitor fuses for a 50 kVAr step typically range from 150 to 200 amps. The fuses are fast-acting and large enough to prevent nuisance fuse blowing on startup. The fuses are designed to interrupt excessive current very rapidly and protect the capacitor cell from catastrophic failure.

The NEC and good practices require overcurrent protection and a means of disconnecting the capacitor system. The conductors, overcurrent device, and disconnecting device must be sized for 135% of the rated current. Compared to the capacitor fuses the response time of the overcurrent device is much slower. The overcurrent device will not trip on momentary surges but will provide the appropriate system protection. NEC requires that the rating or setting of the overcurrent device shall be as low as practicable. The minimum rating for a 50 kVAr step is 81 amps (1.35 x 60).

There is one exception to this requirement: if the capacitor unit is connected to the load side of the motor overload, neither a separate overcurrent device nor a disconnecting means are required. In this case, the reduced current due to improved power factor will impact motor overload rating or setting selection.


MYRON ZUCKER INC. products are designed to:

  • Improve power factor
  • Eliminate utility penalties or surcharges
  • Increase available distribution capacity
  • Mitigate harmonic distortion
  • Protect sensitive equipment
  • Decrease downtime
  • Reduce line losses and associated cost
  • Comply with industry standards

CONTACT US

Myron Zucker, Inc.
36825 Metro Court
Sterling Heights, MI 48312
Toll Free: 800.245.0583
Phone: 586.979.9955
Fax: 586.979.9484
Email: info@myronzucker.com