| CAPACITALK No. 102
WIRES, FUSES AND DISCONNECTS - WHAT SIZE DO I USE?
Wiring power factor capacitors in your electrical system involves determining the proper size wire, fuse and disconnecting means when the power factor capacitor is not part of a motor circuit. The following are some requirements from the National Electrical Code, Article 460:

NEC Article 460-8-b
- An overcurrent device shall be provided in each ungrounded conductor for each capacitor bank.
- The rating or setting of the overcurrent device shall be as low as practicable.
NEC Article 460-8-c
- A disconnecting means shall be provided in each ungrounded conductor for each capacitor bank and shall meet the following requirements:
- The disconnecting means shall open all ungrounded conductors simultaneously.
- The disconnecting means shall be permitted to disconnect the capacitor from the line as a regular operating procedure.
- The rating of the disconnecting means shall not be less than 135 percent of the rated current of the capacitor.

NEC Article 460-8-a
- The ampacity of capacitor circuit conductors shall not be less than 135 percent of the rated current of the capacitor.
Example:
Following the requirements set forth in NEC Article 460, the wire, fuse and disconnect sizes for a 400 kVAR capacitor bank at 480 volt, 60 Hz would be as follows:
400 kVAR x 1.2 amps per kVAR = 480 amps
480 amps x 135% = 648 amps
Disconnect or circuit breaker size = 800 amps
Fuse size = 800 amps
Wire size = (2) 500 mcm per phase
Here is a convenient chart of recommended wire, fuse and switch sizes for 3-phase 60 Hz capacitors - 240, 480 and 600 volts.
|