CAPACIBANK® Brand Capacitor Series
APPLICATIONS
- Branch panel
- Main service entrance
MODELS
- CIM Model: blown fuse indication and CelTel® monitoring system
- CNM Model: blown fuse indication
CELTEL® MONITORING SYSTEM
- Loss-of-capacitance indication
- Indicates when capacitor assembly is no longer functioning effectively
- Phase imbalance indication
- Overcurrent and undercurrent indication
- Reset function
- Self diagnostic function
STANDARD FEATURES
- UL & C-UL listed, CE
- 2-year warranty
- 3-line fusing with blown fuse indication
- Discharge resistors per NEC requirements
- Assembled in the USA
STANDARD RATINGS
- 240, 480, 600 V
- 3-phase
- 60 Hz
CAPACITOR CELLS
- Continuous voltage rating:
- 528 V for 480 V application
- 660 V for 600 V application
- 264 V for 240 V application
- Continuous current rating: 165% of nominal
- Ambient temperature rating: 140° F
- 130,000 hours rated life
- 2-year warranty
- Self-contained, 3-phase, delta-connected
- Industrial grade dry-type construction
- Losses of less than ½ watt per kVAr
- Self-healing metallized polypropylene dielectric film
- 3-phase overpressure disconnector
- Hermetically-sealed aluminum case
- Finger-safe, maintenance free terminals
FUSES
- Fast-acting, current-limiting, with 200,000 ampere interrupting capacity
ENCLOSURES
- Built to NEMA 12 specifications for indoor use
- Wall-mounted or free-standing with hinged door and lockable door handle
- Convection-cooled
FIELD WIRING TERMINATION
- Mechanical connections are provided for all field wiring termination points
- Refer to product manual for incoming conductor information
OPTIONS
- Circuit breaker or disconnect switch
- Other enclosure ratings available
- Other voltage and phase applications available
- Other kVAr configurations available, please contact Myron Zucker, Inc. to speak to an engineer