Phases |
3-phase |
Voltage Rating |
690 VAC max |
Frequency |
Suitable for 50 Hz or 60 Hz systems |
Current Ratings |
3 Arms to over 1200 Arms |
Conductor Material |
PolyGap® reactors: Aluminum Foil; Small reactors: copper wire |
Inductance Tolerance |
– / + 3% in all three phases (Polygap® reactors) |
Inductance Linearity |
5% Z: > 95% inductance at > 190% current
3% Z: > 95% inductance at > 210% current |
Dielectric Strength |
3kV (1 minute) coil-coil, coil-core |
Current Spectrum (see below) |
Calculated using %Z and fundamental current (I1) |
Surrounding Air Temperature |
50oC maximum |
Temperature Rise |
115oC, in 50oC surrounding air temperature |
Insulation System |
Class H, 180oC |
Terminations |
Solid copper bar or tin-plated copper pressure terminal |
Relative Humidity |
Maximum 95% non-condensing |
Agency Approvals |
CUL Listed (E173113), IEC/EN60076-3, VDE0532-76-6, CE Marked |